I-Light Network Operations Report
2024-04-12 - 2024-04-25

I-Light Network Operations Center

Unscheduled Outages Summary

Incident Number Customer Impact Network Impact Title Outage Type Source of Impact Current State Start Time (UTC) End Time (UTC) Duration

INC0171628 2 - High2 - High Outage Resolved - I-Light Backbones IPIU-LFYT & IPIU-SBNDCircuit - Cut Fiber Vendor Closed 2024-04-15 13:07:30 2024-04-16 01:55:54 0 days 12 hr 48 min
INC0171722 2 - High2 - High Brief Outage Resolved - I-Light Backbone EVVL-NEWAUndetermined Undetermined Closed 2024-04-16 08:29:31 2024-04-16 08:30:41 0 days 0 hr 1 min
INC0171754 2 - High2 - High Outage Resolved - I-Light Backbones IPIU-LFYT & IPIU-SBNDCircuit - Damaged Fiber Vendor Closed 2024-04-16 15:59:20 2024-04-17 21:11:29 1 days 5 hr 12 min
INC0171829 2 - High2 - High Brief Outage - I-Light Backbone EVVL-NEWAUndetermined Undetermined Resolved 2024-04-17 08:09:05 2024-04-17 08:10:43 0 days 0 hr 1 min
INC0171930 2 - High2 - High Brief Outage - I-Light Backbones EVVL-NEWA and EVVL-OAKCUndetermined Undetermined Closed 2024-04-18 07:55:19 2024-04-18 07:55:37 0 days 0 hr 0 min

Unscheduled Outages Detail


Ticket No.:INC0171628
Subject:Outage Resolved - I-Light Backbones IPIU-LFYT & IPIU-SBND
Source Of Impact: Vendor
Affected:ILN-IPIU-LFYT-FIBR-1505
Backbone IPIU-LFYT
Backbone IPIU-SBND
Anderson University
Ball State University
Bethel University
DePauw University
Earlham College
FABRIC Operations
Goshen College
Grace College
Holy Cross College
Huntington University
I-Light Engineering & Support
Indiana GigaPOP
Indiana Institute of Technology Ft. Wayne
Indiana University / GlobalNOC
Indiana University East
Indiana University Fort Wayne
Indiana University Kokomo
Indiana University Northwest
Indiana University South Bend
Indiana Wesleyan University
Ivy Tech Connersville
Ivy Tech East Chicago
Ivy Tech Elkhart
Ivy Tech Fort Wayne
Ivy Tech Gary
Ivy Tech Kokomo
Ivy Tech Lafayette
Ivy Tech Lawrenceburg
Ivy Tech Marion
Ivy Tech Michigan City
Ivy Tech Muncie
Ivy Tech Northwest
Ivy Tech Richmond
Ivy Tech South Bend
Ivy Tech Valparaiso
Ivy Tech Warsaw
Manchester University - Ft. Wayne Campus
Manchester University - North Manchester Campus
Purdue Northwest Hammond Campus
Purdue Polytechnic Anderson
Purdue Polytechnic Columbus
Purdue Polytechnic New Albany
Purdue Polytechnic Richmond
Purdue Polytechnic South Bend
Purdue University Ft. Wayne
Trine University
University of Notre Dame
University of St. Francis
Valparaiso University
Vincennes University - Subaru
WBAA, PBS Station W. Lfyt
WFWA - Fort Wayne PBS
WFYI
WNIT - Michiana Public Broadcasting Corporation
Wabash College
Current State:Closed
Start Time:2024-04-15 13:07:30
End Time:2024-04-16 01:55:54
Outgoing Notification TextBackbones IPIU-LFYT & IPIU-SBND are now available. Circuit provider Zayo reported a fiber cut in Lafayette, IN. Zayo crews arrived onsite and located damage where cable was struck by a mower. Crews have completed splicing and all services are restored. Backbone traffic was re-routed via redundant connections.


Ticket No.:INC0171722
Subject:Brief Outage Resolved - I-Light Backbone EVVL-NEWA
Source Of Impact: Undetermined
Affected:ILN-EVVL-NEWA-100GE-24292
Backbone EVVL-NEWA
Hanover College
Indiana State University
Indiana State University Federal Hall
Indiana University Southeast
Indiana University Southeast - Water Tower Square
IU School of Medicine Health Science
Ivy Tech Evansville
Ivy Tech Madison
Ivy Tech Sellersburg
Ivy Tech Terre Haute
Oakland City University
Purdue Polytechnic New Albany
Rose Hulman Institute of Technology
St. Mary of the Woods College
University of Evansville
University of Southern Indiana
Vincennes University
Vincennes University - Fort Branch
Vincennes University - Jasper
Vincennes University - Plainfield
Vincennes University Aviation
Vincennes University Lebanon
Wabash College
Current State:Closed
Start Time:2024-04-16 08:29:31
End Time:2024-04-16 08:30:41
Outgoing Notification TextBackbone EVVL-NEWA is now available following a brief outage. I-Light Engineers have been contacted and the reason for the outage is undetermined.


Ticket No.:INC0171754
Subject:Outage Resolved - I-Light Backbones IPIU-LFYT & IPIU-SBND
Source Of Impact: Vendor
Affected:ILN-IPIU-LFYT-FIBR-1505
Backbone IPIU-LFYT
Backbone IPIU-SBND
Anderson University
Ball State University
Bethel University
DePauw University
Earlham College
FABRIC Operations
Goshen College
Grace College
Holy Cross College
Huntington University
I-Light Engineering & Support
Indiana GigaPOP
Indiana Institute of Technology Ft. Wayne
Indiana University / GlobalNOC
Indiana University East
Indiana University Fort Wayne
Indiana University Kokomo
Indiana University Northwest
Indiana University South Bend
Indiana Wesleyan University
Ivy Tech Connersville
Ivy Tech East Chicago
Ivy Tech Elkhart
Ivy Tech Fort Wayne
Ivy Tech Gary
Ivy Tech Kokomo
Ivy Tech Lafayette
Ivy Tech Lawrenceburg
Ivy Tech Marion
Ivy Tech Michigan City
Ivy Tech Muncie
Ivy Tech Northwest
Ivy Tech Richmond
Ivy Tech South Bend
Ivy Tech Valparaiso
Ivy Tech Warsaw
Manchester University - Ft. Wayne Campus
Manchester University - North Manchester Campus
Purdue Northwest Hammond Campus
Purdue Polytechnic Anderson
Purdue Polytechnic Columbus
Purdue Polytechnic New Albany
Purdue Polytechnic Richmond
Purdue Polytechnic South Bend
Purdue University Ft. Wayne
Trine University
University of Notre Dame
University of St. Francis
Valparaiso University
Vincennes University - Subaru
WBAA, PBS Station W. Lfyt
WFWA - Fort Wayne PBS
WFYI
WNIT - Michiana Public Broadcasting Corporation
Wabash College
Current State:Closed
Start Time:2024-04-16 15:59:20
End Time:2024-04-17 21:11:29
Outgoing Notification TextBackbones IPIU-LFYT & IPIU-SBND are currently available. Circuit provider Zayo was contacted to investigate. Zayo's OSP crews identified damage to approximately 4,000 feet of infrastructure caused by a third party construction company using a boring machine. Splicing has been completed and Zayo is now hands off. No further outages are expected.


Ticket No.:INC0171829
Subject:Brief Outage - I-Light Backbone EVVL-NEWA
Source Of Impact: Undetermined
Affected:ILN-EVVL-NEWA-100GE-24292
Backbone EVVL-NEWA
Hanover College
I-Light Engineering & Support
Indiana State University
Indiana State University Federal Hall
Indiana University Southeast
Indiana University Southeast - Water Tower Square
IU School of Medicine Health Science
Ivy Tech Evansville
Ivy Tech Madison
Ivy Tech Sellersburg
Ivy Tech Terre Haute
Oakland City University
Purdue Polytechnic New Albany
Rose Hulman Institute of Technology
St. Mary of the Woods College
University of Evansville
University of Southern Indiana
Vincennes University
Vincennes University - Fort Branch
Vincennes University - Jasper
Vincennes University - Plainfield
Vincennes University Aviation
Vincennes University Lebanon
Wabash College
Current State:Resolved
Start Time:2024-04-17 08:09:05
End Time:2024-04-17 08:10:43
Outgoing Notification TextBackbone EVVL-NEWA was briefly unavailable. I-Light Engineers have been contacted; however, the reason for the outage is undetermined.


Ticket No.:INC0171930
Subject:Brief Outage - I-Light Backbones EVVL-NEWA and EVVL-OAKC
Source Of Impact: Undetermined
Affected:ILN-EVVL-NEWA-100GE-24292
ILN-EVVL-OAKC-OTU4-24288
Hanover College
Indiana State University
Indiana State University Federal Hall
Indiana University Southeast
Indiana University Southeast - Water Tower Square
IU School of Medicine Health Science
Ivy Tech Evansville
Ivy Tech Madison
Ivy Tech Sellersburg
Ivy Tech Terre Haute
Oakland City University
Purdue Polytechnic New Albany
Rose Hulman Institute of Technology
St. Mary of the Woods College
University of Evansville
University of Southern Indiana
Vincennes University
Vincennes University - Fort Branch
Vincennes University - Jasper
Vincennes University - Plainfield
Vincennes University Aviation
Vincennes University Lebanon
Wabash College
Current State:Closed
Start Time:2024-04-18 07:55:19
End Time:2024-04-18 07:55:37
Outgoing Notification TextBackbones EVVL-NEWA and EVVL-OAKC are currently unavailable. Vendor Zayo Engineers have been contacted; however, the reason for the outage is undetermined.




Upcoming Scheduled Maintenances

Ticket No.:CHG0078497
Subject:Maintenance - I-Light Member WYIN Circuit Testing
Source Of Impact: Internal
Affected:
Start Time:2024-04-26 14:30:00
End Time:2024-04-26 18:30:00
Outgoing Notification Text


Ticket No.:CHG0078499
Subject:Maintenance - I-Light Vendor Smithville Fiber
Source Of Impact: Vendor
Affected:
Start Time:2024-05-01 04:00:00
End Time:2024-05-01 08:00:00
Outgoing Notification TextTBD


Ticket No.:CHG0078472
Subject:Maintenance 1 of 2 - I-Light Vendor Zayo
Source Of Impact: Vendor
Affected:
Start Time:2024-05-15 04:01:00
End Time:2024-05-15 09:00:00
Outgoing Notification TextTBD


Ticket No.:CHG0078473
Subject:Maintenance 2 of 2 - I-Light Vendor Zayo
Source Of Impact: Vendor
Affected:
Start Time:2024-05-16 04:01:00
End Time:2024-05-16 09:00:00
Outgoing Notification TextTBD


Ticket No.:CHG0078301
Subject:Maintenance - I-Light ICTC Data Center Power Maintenance (IPIU)
Source Of Impact: Vendor
Affected:Ivy Tech Indianapolis Central Office
Purdue University
St. Mary of the Woods College
Butler University
Start Time:2024-05-02 11:30:00
End Time:2024-05-02 21:00:00
Outgoing Notification TextIndiana University engineers will be performing a UPS maintenance at the ICTC Data Center. Any members with rack space in ICTC are affected. Partial power loss is expected, and the entire window is reserved.


Ticket No.:CHG0078496
Subject:Maintenance - I-Light Gary: UPS NIC Reseat
Source Of Impact: Internal
Affected:
Start Time:2024-04-26 12:00:00
End Time:2024-04-26 16:00:00
Outgoing Notification Text